  installation tester unilap 100 xe  installation tester as per din vde 0100, ?ve en1, bs, sev and niv  2 years warranty  3 years calibration interval technical data general: display: 3-? digit (1999 ), 7-segment-liquid-crystal- display, 17 mm high, with illumination operating temp. range: 0 c ? + 35 c working temp. range: - 10 c ? + 50 c storage temp. range: - 20 c ? + 60 c reference temp. range: 23 oc 2 oc intrinsic error: refers to the reference temperature temperature coefficient: 0.1 % of m.v. / k operating error: refers to the operating temperature range iec 61557-1 climatic class: jwg as per din 40040 and iec 654-1; relative humidity 65 % annual mean, 85 % max., no damp. protection: ip 40 as per din 40050 and iec 529-2 safety class: class ii ( ) 300 v, install. category iii as per iec 1010-1 / en 61010-1, pollution degree 2. test voltage: 3700 v as per iec 1010-1 / en 61010-1 input protection: by software and varistors against voltages ueff > 600 v and quick-acting fuses (6.3 a / 500 v) max. voltage to earth: ueff = 300 v clearance / creepage distances: correspond to iec 1010-1 / en 61010-1 emission: class b as per en 50081-1 and iec 61326-1 immunity: class a as per en 50082-1 and iec 61326-1 quality standard: as per din iso 9001 auxiliary power: 6 pcs. 1.5 v alkaline manganese batteries (iec lr 6) or accu 7.2 v / 1500 mah (option) dimensions: 265 x 265 x 90 mm (l x w x h) incl. lid and compartment for accessories weight: approx. 2.3 kg without batteries and without accessories approx. 5.7 kg set 1 in carrying case approx. 6.2 kg set 2 in carrying case irda ? interface (infrared data association) as standard. for easy pc- communication (remote control, data acquisi- tion, reading of stored data). integrated data memory for 255 data records (~6000 measurement values). integrated real time clock with date. barcode-reader useable. the limits prescribed by the standards can be adapted individually. a limit infringement is indicated by audible and optical warnings. automatic compensation for standard accessories. compensation for line extensions up to 5  possible. protective conductor check nominal voltage: 50 v ? 300 v ac / 15.3 ... 100 hz between contact electrode and pe-line internal resistance: approx. 1.5 m  phase indication nominal voltage: 20 v ? 300 v ac / 15.3?420 hz internal resistance: approx. 400 k  admiss. overload: max. ueff = 600 v note: the voltage of the "l? and "n? wire is measured to "pe?, evaluated and a symbol indicates the live contact. elmes  heme  norma
2 voltage (dc/ ac), frequency range resolution frequency range operating error 0.. 50..440?550v 1 v dc, 15.3?420 hz (1% of mv +1dig) 15.3..99.9..420hz 0. 1?1hz 5? 440 v (0.1% of mv +1dig) internal resistance: 300?400 k  (l ? n ? pe) residual current operated device check (fi-rcd / iec 61557-6) measuring functions: rcd-test without tripping tripping test with pulses or ramp (tripping time, tripping current) fault voltage loop impedance, short-circuit current (without tripping) earth resistance (with probe) standard/ selective rcds test currents: i  n x1, x2, x5 positive, negative phase position positive, negative pulsating dc current pulses, current steps voltage range: 95 ... 145 v, 175 ... 300 v frequency range: 15.3 ... 17.5 hz, 45 ... 65 hz admissible overload: max. ueff = 600 v rated residual operating current operating error notes i  n (ma) 0.3 x i  n : 10, 0 ? -10 % non-tripping test: 30, 100, 300, 500 of 0.3 i  n 500 / 2000 ms 1 x i  n : 10, 0 ? +10 % with tripping test 30, 100, 300, 500 of i  n pulse, 500 ms 2 x i  n : 10 0 ? +10 % with tripping test 30, 100, 300, 500 of i  n pulse, i  n max = 500 ma 5 x i  n : 10, 30, 100 0 ? +10 % 27?105 % of i  n 10 % of i  n variable rated residual current see above see above 6 ? 1000, resolution 1 ma fault voltage range (u f ) resolution operating error 0.5 ? 99.9 v 0.1 v (0? 8 % of mv. + 2 digit) automatic test stop: u f >50 v complies with iec 1010 tripping time (t a ) resolution operating error 0 ? 500 ms (300 ms) 1 ms 4 ms loop- resolution impedance z s (  ) operating error resp. earth resistance r a 0.2  ?9.99 k  0.01  ?10  (10% of mv. + 4 digit) test current period as per iec 1010-1. limitation of duration period tak- ing into account the fault voltage as per iec 61557-6 and iec 1010-1. positive or negative pulsating direct current: tripping test - corresponding to the applicable standards which admit 0.35 ... 1.4 i  n as tripping current. for ramp function the tripping current is shown as trms of the half-wave current. earthing resistance (ra ext ~) iec 61557-5 measuring method: current / voltage measurement with probe voltage ranges: 95 ... 145 v, 175 ... 300 v, outside these ranges will not be started. frequency ranges: 15.3 ... 17.5 hz, 45 ... 65 hz admiss overload: max. ueff = 600 v before start, (for > 5 v no start), termination of measurement for u eff > 50 v measuring time: max. as per iec 1010, 2 ... 26 periods automatic compensation for standard accessories. compensation for line extensions up to 5  possible. probe voltage resolution operating error 1 ... 70 v 1 v (2 % of m.v. + 1 digit) measuring range resolution operating error 0.01  ...0,15  ...10k  0.1  ... 10  (10% of m.v. + 3 digit) test current: 1 a for < 20  max. interference voltage:for u s-pe > 20v no measurement max. probe resistance: 10 k  , for (r a + r probe ) > 20 k  no start programmable limits: 0.01  ... 9.99 k  earthing resistance (ra int) iec 61557-5 measuring method: current / voltage measurement with probe standard 3-pole measurement and special function 4-pole measurement admiss. overload: max. u eff = 600 v before start (for > 5 v no start), termination of measurement for u eff > 50 v probe resistance: 10 k  , for (r a + r probe > 20k  no start) programmable limits: 0.01  ... 9.99 k  test lead compensation: possible when probe connected (3-pole measurement). measuring time: approx. 3 sec, continuous measurement is possible (3-pole measurement). special function selective earthresistance measurement like standard function but: operating error: (20 % of m.v. + 3 dig) min. current through clip-on current transformer: 1 ma special function stake-less earthing measurement like special function but: measuring range: 0.01...9.9  insulation resistance (riso) iec 61557-2 measuring method: current / voltage measurement nominal output voltage: 100 / 250 / 500 v dc open-circuit voltage: approx. 105 / 260 / 520 v dc nominal current: > 1 ma dc (>2.5 ma dc at 250 v) short-circuit current: < 7 ma dc admiss. overload: max. u eff = 600 v ac; (test is locked) measuring range resolution operating error 1 k  ... 3 k  ... 300 m  1 k  ...1 m  man (8 % of m.v. + 1 digit) 1 k  ... 3 k  ... 10 m  1 k  ... 100 k  auto measuring time: as long as the "start? button is pressed; subsequent automatic discharge of the test piece via 400 k  programmable limit: r iso limit: 1 k  ... 299 m  ( man ) 1 k  ... 9.9 m  ( auto ) auto: test sequence n - pe, l - pe, l - n, programmable dc voltage resolution operating error 1 ... 520 v 1 v (8 % of m.v. + 5 digit) internal resistance: approx. 400 k  (l/n-pe); serves as discharge resistance for any capacitors in the measuring circuit. max. interference voltage:u eff = 1 / 10 of nominal output. no measurement is started at higher voltages. loop impedance (zs/r) l-pe or l-n (l) iec 61557-3 measuring method: voltage drop as per iec 61557 nominal voltage: 95 ... 145 v, 175...300 v, 330 ... 440 v (only l-n (l)) reference voltage: 110 / 230 / 400 v or 127 / 220 /380 v ac or measured voltage frequency range: 15.3 ... 17.5 hz, 45 ... 65 hz
3 z s test current: l-pe l-n(l) voltage range test current zs = 0  zs = 200  x x 55 ... 145 v 2.4...3.61 a 0.2...0.61 a x x 175 ... 300 v 1.75...3.0 a 0.58...1 a x 330 ... 440 v 2.75...3.67 a 1...1.4 a measuring range resolution operating error 0.07 ... 199  0.01  ...1  (5% of m.v. + 3 digit) measuring time : approx. 4 - 50 periods; duration as per iec 1010 mains imped. angle: cos  > 0.5 max. inductance: 5 mh in voltage range > 175 v programmable limit: z s limit : 0.01 ... 199  admiss overload : max. u eff = 600 v ac (measurement is not started outside the admissible voltage and frequency ranges) short-circuit current range display resolution operating error 1 a?10 ka 1?40 ka 1?10?100 a results from i k = u n u n as selected: 1 : 110v, 230v, 400v 2 : 127v, 220v, 380v resp. 3 : measured voltage valid ranges for u n : 95 ? 145 v, 175 ? 300 v, 330 ? 440 v (only at z s l-n ) valid ranges for frequency: 15.3 hz?17.5 hz, 45 hz ? 65 hz earthelectrode fault voltage (sev 3569) earthelectrode voltage, with probe only range resolution measuring method 0?u n 0.1 v u f = r a . i k detection of rotary field direction iec 61557-7 voltage range: 20 ... 440 v ac, 15.3 ... 65 hz admiss. overload: max. u eff = 600 v ac max. current to earth: < 3.5 ma rotary direction display: symbol for right- / left-handed internal resistance: 200 k  ... 400 k  "elliptic rotary fields" with two l-conductors and the neutral conductor can also be tested. low resistance measurements (r1k  ) iec 61557-4 measuring method: current / voltage measurement with automatic pole reversal. open-circuit voltage: approx. 20 v dc short-circuit current: > 200 ma dc admiss. overload: max. u eff = 600 v (before start), no start for > 5 v measuring range resolution operating error 0.01... 0.12 ... 2.99...19.9  ...1k  0.01...0.1...1  (5 % of m.v. + 3 digits) measuring time: approx. 2 s incl. voltage polarity reversal. continous measurement: with depressed start button admissible inductance: max. 5 h programmable limit: r limit 0.01  ... 999  series-mode interference voltage: max. 40 veff ac, in case of higher voltage measurement is terminated. current measurement (with clamp a 6805 01015) sinusoidal ac current 45...65 hz measuring range resolution operating error 1.. 10 ma..199 a 1 ma...1 a (3 % of m.v. + 2 dig) admiss. overload: max l eff = 300 a active power ac voltage and current 45...65 hz, crest factor < 2, cos  > 0.9 u = 50 ... 440 v, i = 20 ma ... 199 a measuring range resolution operating error 0.1.. 1.0... 99.9 k  0.1  ..0.1 k  (3 % of m.v. + 3 dig) admiss. overload: max leff = 300 a max u eff = 600 v energy measurement summing up the active power measured versus time for slowly or rarely variable power. measuring rate: approx. 1hz. measuring range resolution operating error 0.00.. 0.10..99.9 kwh 0.01w ..0.1kwh (3 % of m.v. + 3 dig) apparent power, power factor both quantities are computed values, resulting from the aforemen- tioned quantities and only apply to sinusoidal voltages and currents. continuity test open- circuit voltage: approx. 5 v dc short-circuit current: approx. 10 ma response threshold: < 100  ( 20  ) response time: approx. 20 msec for buzzer indication: continous buzzer tone, display sensor ac (sine, 45...65 hz) - or dc depending on selected function. programmable scale factor and display of important measuring units. meas. range resolution operating error condition 0...10vm...2.99v 1mv/0.01v (2 % + 2 dig) sensor factor = 1 input resistance: approx. 1.5 m  admiss. overload: max u eff = 600 v factor a dc factor a ac 1ma/mv ... 9.99 a / mv factor i x 0.1 i x / mv ... 999 i x / mv factor c 0.01c / mv ...9.99c / mv factor v dc factor v ac 1 mv / mv ... 9.99 v / mv measuring protocol-print in format a4:
order codes description order no. unilap 100 xe incl. carrying case a 1855 06211 at, ch, gb contents: 1 cable (3-pole plug/ 3 safety plugs), 1 cable (3-pole plug/mains plug country specific), 3 alligator clips, 3 test tips, 1 cable (plug / test tip), 1 carrying belt, 2 belt securing devices, 2 earth stakes, 1 cable reel (50 m wire), 1 cable reel (25 m wire), 6 batteries, 1 battery compartment operating instructions in e, d or f unilap 100 xe incl. carrying case contents: a 1855 06212 at, ch, gb 1 cable (3-pole plug/ 3 safety plugs), 1 cable (3-pole plug/mains plug country specific), 3 alligator clips, 3 test tips, 1 cable (plug / test tip), 1 carrying belt, 2 belt securing devices, 2 earth stakes, 1 cable reel (50 m wire), 1 cable reel (25 m wire), 6 batteries, 1 battery compartment operating instructions in e, d or f rs 232 interface accessories barcode-reader a 6914 40300 test probe with start and illumination function a 6914 06110 active temperature probe (type k) -60...800c a 6899 06111 accuset with quick-charging (1.5 ah) a 6403 04111 earth stakes with cable reel (50m) a 6045 10300 pc software winsat 100 a 6899 00182 irda? adapter for pcs a 6412 07000 irda? printer hp deskjet 340 cbi a 6413 06211 measuring set 1 a 6045 10500 measuring set 2 a 6045 10600 clip-on current transformer a 6805 01015 cable for clip-on current transformer a 6002 09100 adapter for stakless measurement a 6002 09018 3 alligator clips a 6009 17103 3 test tips a 6009 54300 mains plug adapter f (nfc61303) - at (schuko) a 6045 06112 adapter for 3-phase outlets a 6009 17200 appliance test adapter a 6045 10200 lem norma gmbh palmersstra?e 2 a-2351 wiener neudorf phone: +43(0)2236 691-0 fax: +43(0)2236 63 080 e-mail: lno@lem.com lem uk ltd geneva court, 1 penketh place, west pimbo skelmersdale, lancashire wn8 9qx phone: 01695 - 720 777 fax: 01695 - 507 04 e-mail: luk@lem.com printed in austria. technical modifications reserved. publication a 99407 e (04.99 5 gd) lem instruments inc. 23822 hawthorne boulevard #100 torrance, ca 90505 phone: 1-310-373-0966 fax: 1-310-373-9056 e-mail: liu@lem.com distributor


▲Up To Search▲   

 
Price & Availability of A-1855-06211GB-UNILAP100XE

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X