Part Number Hot Search : 
BB1L2Q YD78L24 5KP12 DS2155GN 2SC5514 UF16C50 SQ1530 01KS3
Product Description
Full Text Search
 

To Download FXP6000-48-S Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  hot-pluggable model selections model output input voltage range adjustment maximum output line load initial setting voltage 3-phase (vac) range current regulation regulation (note 1) accuracy fxp6000-32-s (note 2) 32v 180 to 264 or 342 to 528 30.5 to 33.5v 175a 0.2% 0.2% 31.93v to 32.07v FXP6000-48-S (note 2) 48v 180 to 264 or 342 to 528 45.6v to 50.4v 125a 0.15% 0.2% 47.90v to 48.10v notes: 1) with remote sense connected. 2) user-selectable input voltage ranges. input specifications parameter description/conditions min nom max units input voltage - ac 3-phase delta low input range, nominal. 200 240 vac 3-phase delta high input range, nominal. 380 480 continuous deviation from the above nominals. -10 +10 % input current per phase at full rated load. fxp6000 at 180 vac: 28 a rms inrush surge current internally limited. vin = 264vac (one cycle). 25 c: 38 a pk vin = 528vac (one cycle). 25 c: 38 input frequency ac input. 50 60 hz hold-up time after last ac line peak at full power. 208 vac: 20 ms 410 vac: 20 operating frequency switching frequency, fixed. 100 khz power factor 0.90 w/va fxp6000 ac-dc series data sheet feb 11, 2005 revised to jan 09, 2007 page 1 of 8 www.power-one.com features ? three-phase ac input ? suitable for 3u or 5u height mounting ? single-wire current share or droop current share ? remote voltage adjust and current monitoring ? overtemperature, overload, and overvoltage protection ? led supply status indicators ? current-share control for up to 30 units ? standard & customized rack adaptors available ? front panel selectable-input-range model availability ? (for higher power requirements, see fxp7000) ? (for chassis-mount requirements, see fxc6000 or fxc7000) fxp6000 front and rear views distributed power front-end the fxp6000 series of rack-mounted power systems provides ac front-end capability to automatic test equipment, telecom, data communications, and other distributed power designs. the fxp systems may be paralleled up to 180 kw of output power. the fxp family is hot pluggable and includes paralleling (or-ing) diodes. these power supplies provide excellent protection against input voltage transients. the fxp family power supplies may be plugged into or removed from an operating system when used in a redundant power configuration. access to interfaces for remote sensing, remote voltage adjust, current sharing, current monitoring, power supply status, standby voltage and inhibit, as well as power connections, is through a connector at the rear of the supply. the fxp has its fan, handles, voltage adjust, and indicator lights on the front panel and a single hot-plug connector on the rear. airflow is from the front through the rear. alarm, monitoring, and control signals are floating from the main output and can be referenced to the positive or negative output or sense line of the power supply. the output is floating with respect to the chassis and may be used as a positive or negative polarity supply. the fxp6000 series meets international safety requirements and is ce marked to the low voltage directive. this series operates on three-phase european voltages as well as (up to) 480vac, delta or wye. description
feb 11, 2005 revised to jan 09, 2007 page 2 of 8 www.power-one.com fxp6000 ac-dc series data sheet output specifications parameter description/conditions min nom max units output voltage an additional 1.0 volt is provided to the output terminals to 32v models: 30.4 32 33.6 adjustment range provide for load lead losses. 48v models: 45.6 48 50.4 v output power continuous duty rating. 32v models: 5600 watts 48v models: 6000 output current continuous duty rating. 32v models: 175 a 48v models: 125 efficiency full rated load (208vac). 32v models: 85 88 % 48v models: 88 91 regulation load, maximum deviation with 0 to 100% load change: with remote sense connected: 0.2 with remote sense not connected: 0.75 % utilizing droop current share: 2.0 line, under all specified operating conditions. 0.2 ripple & noise measured at mating connector w/ 0.01f + 10f tant. 20 mhz bw: 1 % p-p 100 mhz bw: 2 overshoot / undershoot output voltage overshoot/undershoot at turn-on. 0 % minimum loads minimum loading required to maintain regulation. 0 a transient response maximum recovery time, to within 1% of initial set time: 400 s point due to a 25% load change, 1a/s. deviation: 3 % turn-on delay time required for initial output voltage stabilization after power-up. 3 s turn-on rise time time required for output voltage to rise from 10% to 90%. 100 ms interface signals and protection parameter (note 1,2) description/conditions min nom max units ac power fail warning warning provided prior to vout dropping 5% after loss of ac input. 5 ms auxiliary power output voltage - diode isolated. inclusive of line, load, and initial tolerances. 11.5 12.0 12.7 v output current. 500 ma current monitor monitor output current over a compliance range of 0~10v. nominal full load output: 12.5 ma 50-100% load tolerance: -315 0 315 a/a <50% load tolerance: -250 0 500 a/a current share static sharing deviation as a percent of full-load rating active: 5 % for loads >10%. passive: 10 input range select status maximum signal resistance in high input voltage range selection. 0.10  loss of phase warning warning provided prior to protective reduction in current limit. 500 ms output inhibit voltage required to enable supply (0.5 ma sink). (note 3) 1.0 v output interlock voltage required to enable supply (6 ma sink). (note 3) 1.0 v output overload protection straight line current limit (above approx. 5v vout). 32v models: 180 188 a 48v models: 129 134 output overload warning signal level on overload. 2.2 v output short circuit protection occurs on overload when vout is below approx. 5v. 32v models iavg: 30 105 a may operate in burst-mode. 48v models iavg: 21 65 output voltage fault signal deviation from adjusted vout that is considered as a fault. 3 4 5 % output voltage margin output voltage swing available through margin pin (analog). 4.8 5.0 5.2 % overtemperature/ time between fault warning and shutdown. 100 ms fan failure warning latching shutdown. overvoltage protection latch style overvoltage protection. fxp6000-32: 36.3 38.4 40.5 v fxp6000-48: 55.2 57.6 60.0 power supply present signal resistance to logic ground upon insertion of supply. 1000  remote sense maximum load lead loss compensation (round trip). 1.0 v notes: 1) all logic outputs listed below feature a standard active pull-down output with 0.4v max at 40 ma sink capability, and a 100k pull-up to 5v. 2) in addition to those listed below, signals and front-panel leds are provided to indicate: overtemperature/fan fault, ac pha se imbalance, output good, interlock open, and supply inhibited. the fxp also provides 4 led?s indicating output loading. 3) both signals must be pulled to logic ground for the unit to operate. enables are 100% redundant internally for applications where redundant inhibit is desirable. contact factory for additional design details.
fxp6000 ac-dc series data sheet feb 11, 2005 revised to jan 09, 2007 page 3 of 8 www.power-one.com safety, regulatory, and emi specifications parameter conditions/description min nom max units agency approvals ul60950/csa60950-00 (culus), iec60950, en60950 (tv), ce marked for the low voltage directive electromagnetic interference fcc cfr title 47 part 15 sub-part b - conducted. a en55022 / cispr 22 conducted. a class esd susceptibility per en61000-4-2, level 4. 8 kv radiated susceptibility per en61000-4-3, level 3. 10 v/m eft/burst per en61000-4-4, level 4. 4 kv input transient protection per en61000-4-5. line-to-line: 4 kv line-to-ground: 3 voltage sag immunity per semi f47-0200 fxc/fxp7000 pending leakage current per ul60950 and fxp6000 at 240 vac, 60 hz: 5 en60950: fxp6000 at 400 vac, 50 hz: 7 ma fxp6000 at 480 vac, 60 hz: 10 environmental specifications parameter conditions/description min nom max units altitude operating. 10k asl ft. non-operating. 40k operating temperature at 100% load: 0 50 c at 60% load: 70 storage temperature -40 85 c temperature coefficient 0c to 70c (after 15-minute warm-up). .02 %/c relative humidity non-condensing. 95 %rh shock operating: half-sine 10 ms, 3 axis +20 g pk non-operating: half-sine 10 ms, 3 axis +40 vibration operating: swept sine 5-2000-5 hz, 5-32 hz, 0.02?da, 32-2000 hz 1 g pk non-operating: random 10-2000 hz 6.15 grms airflow airflow provided through the supply from front to rear. 135 cfm 3.8 m 3 /min 483 lfm 2.5 m/s weight 29 lb 13 kg nuclear and medical applications - power-one products are not designed, intended for use in, or authorized for use as critical c omponents in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written conse nt of the respective divisional president of power-one, inc. technical revisions - the appearance of products, including safety agency certifications pictured on labels, may change dependin g on the date manufactured. specifications are subject to change without notice.
tyco pn elcon pn description 1648601-1 296-22-01100 conn hsing fem 52p top drawer 1648420-1 712-12-01107 contact socket #0 double crown 1648318-1 702-32-01107 conn socket #12 blind mate 1648325-1 702-92-01109 conn socket #20 blind mate feb 11, 2005 revised to jan 09, 2007 page 4 of 8 www.power-one.com fxp6000 ac-dc series data sheet bottom view side view a a a a a a a a aa a a a a a a < --airflow lock handle 16.09" (408.7mm) 14.259" (362.18mm) 5.750" (146.05mm) 1.100" (27.94mm) 0.480" (12.19mm) 16.96" (430.8mm) 1.759" (44.68mm) 4.000" (101.6mm) 15.462" (392.73mm) 4.954" (125.83mm) 0.87" (22.1mm) 8.00" (203.2mm) 0.204" (5.18mm) 0.649" (16.48mm) 0.590" (14.99mm) 0.341" (8.66mm) 7.509" (190.73mm) 11.704" (297.28mm) led handle lock hook note: total bottom stackup of rack must be no greater than 0.204". for optional hard mounting, use m4 x 0.7 screws, 8pl (marked a) on side or bottom with maximum penetration 3.8mm. recommended mounting torque 10.5 inch lbs. (0.64n/m) rear view 2.437" (61.90mm) 3.901" (99.09mm) 0.521" (13.24mm) front view 5.000" (127mm) 0.222" (5.64mm) 0.090" (2.29mm) 2pl 4.552" (115.62mm) 0.226" (5.74mm) lock handle release center -to- center input voltage display cutout c l c l maintain 25 sq in min free area (front and rear) for air cooling 480vac input voltage range select module rotate 180 degrees for 240 vac when using the fxp6000-32-s or FXP6000-48-S models input voltage label here for fxp6000-32-240 or fxp6000-48-240 fxp6000 overall size: 16.96" x 8.00" x 5.00" (430.8mm x 203.2mm x 127.0mm) mating connector information
fxp6000 ac-dc series data sheet feb 11, 2005 revised to jan 09, 2007 page 5 of 8 www.power-one.com 0.129" 4pl (3.28mm) 1.484" 2pl (37.69mm) 19.000" (482.6mm) 5.215" (132.46mm) 2.250" 2pl (57.15mm) 18.312" (465.12mm) fxp6000 2pl frh7000 power shelf, front view note: fxp6000 power supplies are shown for illustration purposes only and are not included as part of power shelf assembly. 480vac 480vac j2 ac inputs j3 3 phase 3 wire + pe j1 - + 1 2 3 frh7000 power shelf, rear view 0.000 0.000 unit label 0.61" (15.5mm) 3.56" (90.4mm) 5.215" (132.46mm) 2.74" (69.6mm) 4.38" (111.25mm) 9.42" (239.27mm) 15.14" (384.56mm) 16.84" (427.74mm) 17.14" (435.34mm) 19.000" (482.6mm) 0.66" (16.76mm) 1.86" (47.24mm) 10/32 ground stud 2pl amp pn 213581-1 with silver-plated contacts 15.44" (384.56mm) pin 1 5/16-18 stud 2 pl accomodates ring lug 1.08 max width 2 pl 2 pl 2 pl notes: 1. for clarity, finger guard for dc output terminals is not shown in this illustration. 50-pin signal header with keying and latches (amp pn: 1-499141-0) attach earth gnds before ac connectors ? note: the frh7000 power shelf is designed for alternative vertical mounting with the right side down.
feb 11, 2005 revised to jan 09, 2007 page 6 of 8 www.power-one.com fxp6000 ac-dc series data sheet this kit is used to cover an unused right-side slot of the frh7000 power shelf (as viewed from the front of the frh7000). the kit can be installed before, or after installation of the power shelf into the rack. frh7000 power shelf, right-side view 21.91" (556.5mm) 24.000" (609.6mm) 4.000" (101.6mm) 0.715" (18.16mm) 1/4-20 inserts 2 pl each side for rear support customer-supplied cables or bus bars rack mounting flange bracket 101363 or 103040 as appropriate filler panel bracket 101363 (filler panel kit as seen from inside of power shelf)
fxp6000 ac-dc series data sheet feb 11, 2005 revised to jan 09, 2007 page 7 of 8 www.power-one.com - dc out + - d c o u t + 12 1 2 3 5/16-18 stud 2pl accomodates cable lug 1.08" width max. 50-pin signal header with keying and latches ( amp pn: 1-499141-0 ) pin 1 j2 ac inputs j3 3 phase 3w + pe 10/32 pe stud 3p l amp pn: 213581-1 with silver-plated pin contacts j1 j4 3.55" (90.17mm) 1.01" (25.65mm) 0.40" (10.16mm) 3.31" (84.07mm) 4.95" (125.73mm) 9.42" (239.27mm) 13.37" (339.60mm) 13.67" (347.22mm) 15.07" (382.78mm) 15.37" (390.40mm) 16.77" (425.96mm) 17.07" (433.58mm) 2.71" 3pl (68.8mm) 1.07" 3pl (27.2mm) 0.000 0.000 unit label frv7000 power shelf, rear view notes: 1. for clarity, finger guard for dc output terminals is not shown in this illustration. attach earth gnds before ac connectors 18.656" 2pl (473.86mm) 0.344" 2pl (8.74mm) 0.000 19.000" (482.6mm) 8.70" (221.0mm) 7.184" 2pl (182.47mm) 1.434" 2pl (36.42mm) r 0.129" 4pl (3.28mm) 0.000 frv7000 power shelf, front view note: fxp6000 power supplies are shown for illustration purposes only and are not included as part of power shelf assembly. input voltage range select module input voltage display cutout 480vac 480vac 480vac ?
feb 11, 2005 revised to jan 09, 2007 page 8 of 8 www.power-one.com fxp6000 ac-dc series data sheet filler panel kit, pn: 088-101348 (used with frv7000 power shelf) this kit is used to cover an unused left or center slot of the frv7000 power shelf (as viewed from the front of the frv7000). one kit is required per slot. kits can be installed before, or after installation of the power shelf into the rack. frv7000 power shelf, left-side view 25.56" (649.2mm) 0.000 7.20" (182.9mm) 1.20" (30.5mm) 0.40" (10.2mm) 0.214" (5.44mm) 0.000 cooling air exhaust cooling air intake customer-supplied dc cables power supply lock hook; clearance required 6 places finger guard for dc output terminals 24.00" (609.6mm) 22.50" 2pl (571.5mm) 1/4-20 threaded inserts 2pl each side for rear support of unit. do not exceed 0.500" penetration of screw into unit. (filler panel kit as seen from inside of power shelf) filler panel upper bracket lower bracket


▲Up To Search▲   

 
Price & Availability of FXP6000-48-S

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X