  ldp 200 - 200 is the first user programmable unit on the market that can supply any voltage between 36 and 205 vdc, offering unmatched flexibility for many applications. its compact size, high efficiency, excellent reliability together with easy installation makes it ideal for various industrial applications. ldp200 - 200 is class i isolation device suitable for selv and pelv circuitry and is designed to be mounted on din rail and installed inside a protective enclosure. ? high efficiency and compact size ? active pfc ? wide input voltage range 170 - 550 vac ? wide output voltage range 36 - 205 vdc, user settable ? 2 user programmable voltage steps with settable duration ? digital control ? remote on/off or other remote control functions possible through enable input ? multiple protections ? ideal for elevator application ? excellent versatility, allowing parts stock savings ? up to 50c operating temperature with no derating ? industrial control ? communication ? instrumentation equipment ? renewable energy systems
2 ldp200 - 200 tech.support@psbel.com ldp200 - 200 230 / 400 v ( range 1 70 - 550 va c) 36 - 205 v dc 2.3 a max * * 2.3 a max. for vout < 80 v. for vout > 80 v output is limited by output power 187 w max. technical parameters are typical, measured in labor atory environment at 25c and 40 0 vac / 50 hz, at nominal values, after minimum 5 minutes of operation. input ac voltage range 1 s ingle or two p hases operating 200 - 500 vac 170 - 550 vac input dc voltage range 250 C 725 vdc input frequency 47 - 63 hz input ac current v in = 200 vac v in = 500 vac 1.4 a 0.5 a input dc current vin = 250 v dc vin = 725 vdc 1.4 a 0.7 a power factor correction active > 0.9 standby p ower < 6 w inrush peak current 50 a touch (leakage) current 0.3 ma internal protection f use none, external fuse must be provided recommended external protection it is strongly recommended to provide external surge arresters (spd) according to local regulations. mcb 6 a , c curve or 4a d curve 1 cb scheme certified up to 528 vac. output power 200 w rated voltage 1 v resolution programmable 36 C 205 vdc continuous current or v out x iout = max. 187 w for v out > 80 v max 2.3 a overload limit 2.4 a short circuit peak current 2.5 a load regulation 1% ripple & noise 2 6 00 mvpp hold up time 30 ms protections overload and short circuit with constant current (3 s) and one shot (no auto recovery) thermal protection input undervoltage lockout (uvlo) input overvoltage protection (vdr) status signals 7 segment, 3 digits display 3 programming keys enable - insulated rem ote on/off input, active for 12 - 230 vac/dc parallel c onnection possible with external oring module efficiency > 87 % dissipated power < 28 w 2 ripple and noise are measured with 20 mhz bandwidth, probe terminated with a 0.1 f mkp parallel capacitor.
ldp200 - 200 3 asia - pacific +86 755 298 85888 europe, middle east +353 61 225 977 north america +1 408 785 5200 ? 2016 bel power solutions & protection bcd.00761_ a b operating temperature overtemperature protection start - up type tested: - 40oc 3 - 40 to + 7 0c temperature derating d o not exceed v out x iout = max. 100 w at 70c - 4.2 w/oc over 50oc humidity non - condensing 5 C 95% rh life time expectancy a t 25c ambient full load 716864 h (8.1 years) overvoltage category pollution degree ii i ( en50178 ) 2 ( iec60664 - 1 ) isolation voltage input to output input to ground input to enable output to ground output to enable enable to ground 4.2 kvdc 3.4 kvdc 4.2 kvdc 1.65 kvdc 4.2 kvdc 4.2 kvdc safety standards & approvals ul508 (reference) en60950 (certified) en50178 (reference) emc standards emission: en55011 (cispr11) en55022 (cispr22) en12015 en61000 - 3 - 2 class a class a class a class a immunity: en61000 - 4 - 2 en61000 - 4 - 3 en61000 - 4 - 4 en61000 - 4 - 5 en61000 - 4 - 11 en12016 level 3 level 3 level 3 level 4 level 2 protection degree en60529 ip20 vibration sinusoidal iec 60068 - 2 - 6 (5 - 17.8 hz: 1.6mm; 17.8 - 500 hz: 2 g 2 hours / axis (x,y,z) shock iec 60068 - 2 - 27 (30 g 6 ms, 20 g 11ms; 3 bumps / direction, 18 bumps total) 3 possible at no minal voltage with load derating . note: power rating, losses, efficiency, ripple, thermal behaviour and start - up may change outside of the nominal rated input range. contact factory for details. weight 0.75 k g dimensions (w x h x d) 80 x 120 x 10 2 mm mounting rail iec 60715/h15/th35 - 7.5( - 15) connection terminals screw type pluggable (24 - 12 awg) 2.5 mm2 case material aluminum
4 ldp200 - 200 tech.support@psbel.com figure 1 . mechanical dr awing pin description 1 ac/dc input 2 enable input 3 dc output (load) 4 display 5 set button 6 increase button 7 decrease button input connection o utput connection single phase: l1 = line n = neutral = earth ground + = positive dc - = negative dc two phase: l1 = phase 1 l 2 = p hase 2 = earth ground dc: l1 = + positive dc l2 = - negative dc = earth ground enable: (12 C 230 vac/dc) e+ = positive dc e - = negative dc nuclear and medical applications - products are not designed or intended for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems. technical revisions - the appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. specifications are subject to change without notice.


▲Up To Search▲   

 
Price & Availability of LDP200-200

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X